Compatibility Tool
Utilize our compatibility tool for dangerous goods to enhance the effectiveness of minimizing the risk associated with storing incompatible hazardous chemicals and goods.
Please note: This compatibility tool is intended as a guide and should not substitute a safety data sheet (SDS) or a risk assessment.
The tool should only be employed for dangerous goods in workplaces where hazardous chemicals are stored.
Do not use the tool for:
- Transport situations, where the ADG code should be applied.
- Application against open (in use) packages kept on a shelf or benchtop within a laboratory, workshop, or similar setting.
Note: Radioactive materials (class 7) and explosives (class 1) should be considered incompatible with all other dangerous goods.
How to use the tool:
- Identify whether the material is dangerous goods or a combustible liquid (a combustible liquid has a flashpoint above 60°C) using the SDS/label.
- Identify the class, subsidiary risk, and packing group (where relevant) of each of the two dangerous goods you intend to store together.
- For goods that are also combustible liquids, consider this as a 'subsidiary risk' for evaluation.
- Use the chart provided to ensure compatibility by aligning the vertical and horizontal axes.
- Check and repeat this process for any subsidiary risks associated with either of the goods.
- It is recommended to consult the SDS to ensure materials are compatible. Goods with different UN numbers within the same class may be incompatible.
- Follow the provided directions using the compatibility chart, checking all guidance notes and supplementary notes.
- For incompatible goods, consider greater separation if the packing group is PG I or II, irrespective of the symbol used, to account for the higher level of danger.
Compatible Goods: Two or more goods are considered compatible if their interaction does not result in:
- Harm to persons, property, or the environment.
- Fire, explosion, or the generation of toxic, flammable, or corrosive vapors/gases.
- Acceleration of the combustion of other goods/liquids in the event of a fire.
- Release of contents leading to the premature degradation/corrosion of packaging/means of containment for other dangerous goods or combustible liquids.
- Interaction of dangerous goods/combustible liquids with incompatible firefighting or dispersal media during a fire/spill/release event. Some materials are water-reactive and should be stored away from goods reliant on water or foam as firefighting/dispersal/suppression media.
Compatibility and Segregation Chart: The segregation chart is provided to help minimize the risk of storing incompatible goods. It acknowledges that transport guidelines may not be suitable for workplace situations, where larger quantities of goods may be stored together under better control measures. Scroll to the right to view the full table.
Class of goods | 2.1 | 2.2 | 2.2 SR 5.1 | 2.3 | 3 | 4.1 | 4.2 | 4.3 | 5.1 | 5.2 | 6.1 | 8 | 9 | Combustible liquids |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
2.1 | ||||||||||||||
2.2 | ||||||||||||||
2.2 SR 5.1 | ||||||||||||||
2.3 | ||||||||||||||
3 | ||||||||||||||
4.1 | ||||||||||||||
4.2 | ||||||||||||||
4.3 | ||||||||||||||
5.1 | ||||||||||||||
5.2 | ||||||||||||||
6.1 | ||||||||||||||
8 | ||||||||||||||
9 | ||||||||||||||
Combustible liquids | ||||||||||||||
May be compatible in many cases with exceptions. Follow the compatible goods guidance notes. | ||||||||||||||
Likely to be incompatible. Segregation strongly recommended, follow the segregation of guidance notes for incompatible goods. |
Segregation guidance notes for incompatible goods
S1 | Segregate these goods by 3m or more in a well ventilated area. For liquid dangerous goods the distance is measured from the edge of the spill catchment area. See supplementary notes 6 and 7 |
---|---|
S2 | Segregate by 5 m or more. If one of the dangerous goods is a liquid, measure the distance from the edge of the spill catchment area. Liquid dangerous goods should be located within a separate spill catchment area. See supplementary notes 6 and 7 |
S3 | Segregate by 3 m or more for PG III goods and 5m or more for PG II, PG I goods or where the goods may react dangerously. If both are solids then a minimum of 1m separation may be used. Where one of the goods is a liquid the distance is measured from the edge of the spill catchment area. See supplementary notes 6 and 7 |
S4 | Segregation preferred by the use of fire-rated partitioned areas. Consider use of separate detached building for organic peroxides and for highly pyrophoric class 4.2 goods |
S5 | Segregation of class 4.3 preferred by use of a separate, detached building without water based fire suppression system |
Compatible goods guidance notes
A | In most cases materials of the same class will be compatible. However, not all materials with different UN Numbers will always be compatible. The SDS should be checked |
---|---|
B | In many cases the goods will be compatible. Must check for subsidiary risk compatibility and the SDS |
C | If one of the goods present is also a fire risk substance (one of class 2.1, 3, 4, 5, a combustible liquid or has a subsidiary risk of one of these) or elevated temperature goods, segregation is required by at least 3 m or more. Sub-risk MUST be considered. Other exceptions apply. Check the SDS |
D | Not all class 5.1 goods are compatible as follows:
|
E | Organic peroxides are highly reactive materials. Please check the SDS to ensure compatibility |
F | Where one of the goods to be stored together is a concentrated strong acid and the other a concentrated strong alkali, they should be deemed incompatible |
G | Class 4.3 goods must not be stored next to goods that are in a solution containing water, or where water or foam is the chosen firefighting/spill/leak dispersal or suppression media for the storage area |
H | Except where the class 6.1 is cyanide and the class 8 an acid. Check the SDS |
I | Toxic gases ammonia and chlorine must be segregated due to risk of explosion. It is important to refer to the SDS for incompatibilities within this class division. It is strongly recommended that each different toxic gas (Class 2.3) be segregated unless information in the SDS says otherwise |